Technical data

FIRE ALARM LINES

 
– Maximum number of fire detectors in a line 32  
– Connecting line two-wire  
– Maximum resistance of a line 100Ω  
CONTROLLABLE OUTPUTS  
– Type potential  
– Electrical characteristics (24±5)V/100 mA  
RELAY OUTPUTS FOR FAULT CONDITIONS  
– Type potential free, switching  
– Electrical characteristics 3 A/125 V AC; 3 A/30 V DC  
RELAY OUTPUTS FOR FAULT CONDITIONS  
– Type potential free, switching  
– Electrical characteristics 3 A/125 V AC; 3 A/30 V DC  
INDICATIONS OF REGISTERED EVENTS  
– Light indication LEDs  
– Text messages LCD display – 1 line, 16 symbols, Latin/Cyrillic characters, backlit  
– Sound Built-in sounder  
ACCESS LEVELS TO CONTROL FUNCTIONS 4 (in compliance with EN 54/2)  
POWER SUPPLY  
– Voltage 220/230 V  
– Frequency 50 Hz  
BACKUP BATTERIES 2 x 12 V / 7 Ah  
OPERATION IN DUTY MODE UPON INTERRUPTED MAINS SUPPLY
– Minimum configuration 46 h
– Maximum configuration 32 h
CONSUMPTION ON BACKUP BATTERIES SUPPLY IN DUTY MODE AT 24 V
– Minimum configuration <150 mA
– Maximum configuration <220 mA
POWER SUPPLY TO EXTERNAL DEVICES
– Voltage (24±5)V
– Maximum current value (current of controllable outputs included) 1,3 A
WEIGHT (BACKUP BATTERIES NOT INCLUDED) 5,2 kg
DIMENSIONS 445 x 327 x 87 mm
OPERATING TEMPERATURE minus 5 oC to +40 oC
RELATIVE HUMIDITY to 93 %
DEGREE OF PROTECTION IP 40


Extention modules:

5101 – Extention module

– 3 fire alarm lines.

– 3 relay outputs for fire

5102 – Extention module

– 6 fire alarm lines

– 3 relay outputs for fire


RS232/485 Interface module – provide communication between fire alarm control panels types FS5100, FS5200 and FS4000 with repeater type FS5200R products of UniPOS.

Possible configurations:

Configuration name Description Configuration
FS 5100 basic configuration – 2 fire alarm lines

– 2 controllable outputs

– 2 relay outputs for fire

FS 5100 + 5101 – 5 fire alarm lines

– 2 controllable outputs

– 5 relay outputs for fire

FS 5100 + 5102 – 8 fire alarm lines

– 2 controllable outputs

– 5 relay outputs for fire